Laike K8001 Series Water Air Conditioner Dual Probe Fan Coil Unit Thermostat Manual

Mondo Finance Updated on 2024-01-31

Laike K8001 series water air conditioner dual probe fan coil unit thermostat, with a unique double probe design, is widely used in water air conditioning fan coil units and other places, not only to control the indoor temperature, but also to detect the pipe temperature, to prevent cold air from blowing indoors in winter.

Note: There are three wiring methods for K8001 series water air conditioner dual probe fan coil unit thermostat!Please choose product !! with different wiring methods according to your actual situationThey have the same function except for the different wiring methods and probes.

Display & Key Description:

Function Description:

Mode Selection:Press ".M keyThe LCD displays "Cool Air" for cooling mode, "Warm Air" for heating mode, and "Ventilation" for ventilation mode.

Wind speed selection:Press ".Wind speed built"Select the wind speed of the fan: high, medium, low, automatic.

In "Auto" mode, the wind speed is automatically shifted, i.e. when the room temperature differs by 1 from the set temperature, the low speed is automatically selectedWhen the room temperature differs by 2 from the set temperature, the medium speed is automatically selectedWhen the room temperature is 3 or more different from the set temperature, the high speed is automatically selected.

Timed power-on:When the device is turned on, press and hold ".Clock keysSwitch to timer power on in 3 seconds, display "Timer on", then press the "clock button" to select the minute and clock, press the " button to adjust the timing time, and wait for 5 seconds after the adjustment is completed and automatically saved. After the timer start function is turned on, the fan will be turned off immediately when the machine is turned on, and the fan will be turned on immediately after the set time is reached.

Timed shutdown:When the device is turned on, press and hold ".Clock keysThe button switches to timer power on for 3 seconds, and the display of "timer on" is displayed, and then continuously short presses".Clock keyskey until Timer Off is displayed, and then press ".Clock keys"" key to select the minute, clock, press the " " button to adjust the timing time, after the adjustment is completed, wait for 5 seconds and then save automatically. When the timer shutdown function is turned on, the thermostat will automatically shut down and the fan will be turned off at the same time when the set time is reached.

Heating Mode Activation Conditions:The heating unit starts to run when the mode is selected as "Warm air", the set temperature is higher than the room temperature, and the water temperature detected in the lower right corner of the screen is higher than 30 (adjustable in item 3 of the advanced option).

Advanced option setting: In the shutdown state, press and hold the "M" button for 5 seconds to enter the advanced option setting, the serial number will be displayed on the left side of the screen, and the corresponding parameters will be displayed on the right side, press the "M" button to switch options, and the power will be automatically saved after adjustment.

Installation diagram:

Cut off the power supply during installation. Configure a power switch to cut off the power when it is not heating.

The installation position should be 1 from the groundAbout 4m, avoid direct sunlight, shelter from wind, away from heat sources, and have a representative location of room temperature.

Connect the circuit according to the backshell wiring diagram. If the thermostat used does not match the installed drawing, please contact the dealer or factory.

Load is equipped according to the indicated current, and overload is prohibited.

Please refer to the wiring diagram provided for the correct wiring