1. The shock absorber should be symmetrically arranged according to the central axis of the pump unit. The shock absorbers can be arranged in a clockwise or counterclockwise direction.
2. When the unit shock absorber has six installation points, four of them should be arranged on the four corners of the inert block or steel frame, and the other two should be installed on the long sideline, and their position should be adjusted to ensure that the compression set of the shock absorber should be as consistent as possible.
3. When installing the damping spring shock absorber on the horizontal water pump unit, under normal circumstances, the shock absorber should be fixed with the ground, inert block or steel frame with connecting female.
4. When the vibration isolator is used in the vertical pump unit, a steel base should be installed under the base of the pump unit and anchoredThe steel base and the shock absorber should be bolted (with spring washers) to fix. Anchor bolts are provided on the ground or floor, and shock absorbers are fixed on the ground or floor through anchor bolts.
5. The edge line of the shock absorber shall not exceed the edge line of the inert block;The supporting area of the steel frame shall not be less than the area of the shock absorber.
6. Inspection should be carried out in time before construction and installation. When installed, the static compression deformation of the shock absorber should not exceed the maximum permissible value.
7. When installing the pump unit, the supporting ground of the pump unit must be flat and have sufficient bearing capacity.
8. The shock absorber of the unit should avoid contact with acids, alkalis, organic solvents and other substances.