Dr. Rexroth drive E3115 early warning information maintenance method summary

Mondo Technology Updated on 2024-01-29

Rexroth drive repair: E3115 Brake Test Interval End of Time Warning Information. If the "Hold Brake Monitoring Time Interval" has been activated in the P-0-0525, Hold Brake Control word, the controller determines the time that has elapsed since the last time the hold brake was checked.

Cause: The drive unit has entered the operating state, followed by a fault report F3115. Only the fault information was deleted, but the brake test was not performed.

The interval since the last time the holding brake was monitored is 15 minutes or less different from the interval set in P-0-0550, Brake Test Interval.

Workaround: Start the brake test within 15 minutes of the start of operation of the drive.

P-0-0541, C2100 Instruction Brake Monitoring).

Brake testing begins within 15 minutes of the appearance of the E3115.

P-0-0541, C2100 Instruction Brake Monitoring).

Summary of Dr. Rexroth drive repair methods:

Rexroth DKC series servo drive reported F860 maintenance.

Rexroth DKC series servo drive reported C212 for maintenance.

Rexroth DKS series servo drive shows 61 repairs.

Rexroth DKS series servo drive without display maintenance.

Rexroth DKS series servo drive shows 25 repairs.

Rexroth DKS series servo drive display 67 repair.

Rexroth RAC series servo drive reported feedback repair.

Rexroth RAC series servo drive reported NO24V for maintenance.

Rexroth RAC series servo drive reported for phase maintenance.

Rexroth RAC series servo drives reported to S-Circuit for repair.

Rexroth TDV series servo drive H1B light does not light up for maintenance.

Rexroth TDV series servo drive H2B light does not light up for maintenance.

Rexroth TDV series servo driver H1A lamp does not light up for maintenance.

Rexroth HVE series servo drive without display maintenance.

Rexroth HVE series servo drives show 82 repairs.

Rexroth HVE series servo drives show 25 repairs.

Related Pages