How to collect fluoride in air conditioners, and what is the specific operation method for recoverin

Mondo Finance Updated on 2024-01-31

Before the air conditioner is moved, the first thing to do is to refrigerate, that is, to put the refrigerant into the outdoor unit to avoid the leakage of refrigerant inside the air conditioner

1. The specific operation method of the refrigerant is as follows:

1.Remove the bonnets of the gas and liquid shut-off valves and confirm that the valve doors are in the open position.

2.After starting the air conditioner for 10 to 15 minutes, stop the operation and wait for 3 minutes, then connect the composite repair valve to the process nozzle of the three-way shut-off valve.

3.Open the low-pressure valve of the composite repair valve and expel the air from the connecting hose. Use an Allen wrench to turn the stem in a clockwise direction to close the two-way globe valve.

4.When the gauge pressure of the low pressure gauge is 0 MPa (at this time, frost will form on the two-way shut-off valve), turn off the air conditioner and stop the air conditioner.

5.Then use an Allen wrench to rotate the stem of the three-way globe valve in a clockwise direction to the end to close the three-way globe valve. At this time, the refrigerant operation is completed, and the air conditioner can be disassembled and relocated after the refrigerant.

2. Precautions for refrigerants.

*Refrigerant precautions are as follows:

1.In the first refrigerant, the action of closing the three-way globe valve should be rapid, and the valve should not stay in a half-open and half-closed state, otherwise there will be air entering the refrigeration system.

2.Attention should be paid to whether the shut-off valve is leaking. In the case of ** refrigerant, if you see condensation in the low-pressure liquid pipe, it means that the shut-off valve has a fault of air leakage, and the ** refrigerant should be stopped at this time, and measures should be taken to fill the leakage in time.