DSE6110 DSE6110 MKII DSE6110 MKIII mains failure self starting control module

Mondo Technology Updated on 2024-02-21

British deep-sea DSE6110, DSE6110 MKII, DSE6110 MKIII self-starting mains failure self-starting controller.

The DSE6110 is a stand-alone self-starting controller, and the DSE6120 is a mains fail-safe self-starting controller.

The DSE6110 20 is used to control a single generator set, supports multi-Chinese display, and can be connected to an expansion module.

Real-time clock, fuel pump control function, 4 active outputs.

4 analog inputs digital inputs, 6 custom digital inputs.

It can be connected to DSE2130, DSE2157, DSE2548 expansion modules, and can support 0-10V or 4-20mA oil pressure sensors.

It has the function of graded loading, supports EFI and non-EFI engines, and can set 3 maintenance alarms.

Engine speed protection, engine warm-up, multiple start-stop cycles can be preset.

Engine start-up idle > shutdown idle battery voltage monitoring.

When the battery voltage is low, the unit is started with a customized remote start signal.

It can preset two sets of protection parameters, three types of alarm levels, LCD and LED alarm indications, and 100 event records.

The DSE6110 20 controller is suitable for diesel, gas, and gasoline engines; Support EFI and non-EFI engines.

The DSE6110 20 controller has flexible inputs, outputs, and protection to meet the needs of most applications.

The LCD display of the DSE6110 20 controller can display alarm information such as common alarms, electrical trips and shutdowns, and can monitor the engine speed, oil pressure, water temperature, oil level, as well as the frequency, voltage, current and power of the generator, providing perfect engine and generator protection.

The program can be set up via the DSE software and all parameters can be edited from the front panel.

Dimensions (mm): 216 x 158 x 43

Cutout size (mm): 184 x 137

Panel thickness: 8 mm

Custom input: negative signal input 0 480

Output A (Fuel): 10 A DC short time output, 5 A DC continuous output.

Output B (start): 10 A DC short time output, 5 A DC continuous output.

Custom outputs c, d, e & f: 2 A DC output.

Storage temperature: -40 85

Operating temperature: -30 70

Cryogenic version of the controller operating temperature: -40 70