The installation height of various types of sockets is summarized

Mondo Home Updated on 2024-03-08

Technical Regulations on the Design of Indoor and Outdoor Power Distribution of Residential Projects (Trial) CJS01-2013, 54. Household socket setting: The capacity of the socket should meet the safe operation requirements of the maximum load, and the installation height of the socket is 1When 8m and below, a safety socket should be used

Safety socket: Code for Residential Buildings J 10968-2013, 85.5. The power socket and lighting in the residential suite should be distributed separately. Installed in 1Sockets of 8m and below should be safety sockets. Safety socket: Code for Electrical Design of Residential Buildings JGJ 242-2011, 85.5. All electrical outlets in residential buildings are at a distance of 1When 8m and below, products with safety doors should be selected. Shower toilet socket: Code for electrical design of residential buildings JGJ 24-2011, 85.6. For toilets equipped with showers or bathtubs, the bottom margin of the electric water heater power socket should not be less than 23m, exhaust fans and other power sockets should be installed in zone 3. Body air conditioners, range hoods, exhaust fans, electric water heater power sockets, kitchen electric cookers, washing machines: code for electrical design of residential buildings" JGJ 242-2011, 85.4. The power sockets in the new residential buildings should be concealed, and the power sockets in the living room (hall), bedroom and study should be set on different walls. The bottom margin of the power socket of split air conditioners, range hoods, exhaust fans, and electric water heaters should not be less than 18m;The bottom margin of the electric cooker and washing machine power socket in the kitchen should be 10m~1.3m;The bottom margin of cabinet air conditioners, refrigerators and general power sockets should be 03m~0.5m。

Sockets in children's activity areas: Code for Electrical Design of Shop Buildings JGJ 392-2016, 45.4. The electrical equipment of the store building shall comply with the following regulations: power outlets should not be set up in the children's activity area. When there is a setting requirement, the installation height of the socket from the ground should not be less than 18m, and a safety socket should be selected. Sockets for primary and secondary schools and kindergartens: Code for electrical design of educational buildings" JGJ 310-2013, 52.4. The power sockets of primary and secondary schools and kindergartens must be safe. The bottom margin of the power socket in the children's activity place should not be less than 18m。Nursery and kindergarten sockets: Code for the architectural design of nurseries and kindergartens JGJ 39-2016 (2019 edition), 63.5. Sockets should be set up in the rooms of nurseries and kindergartens, and the location and number should be determined according to the needs. There should be no less than four sets of sockets in the activity room and no less than two sockets in the dormitory. The socket should be of the safety type, and the installation height should not be less than 180m。The socket circuit and the lighting circuit should be set up separately, and the socket circuit should be provided with residual current action protection, and its rated action current should not be greater than 30mA. Electrical shaft sockets: Tianjin Residential Design Standard J 10968-2013, 140.8. The setting of the electrical shaft shall meet the following requirements: in the weak current shaft (including the strong and weak current combined shaft) of the active equipment of the weak current system, a 220V three-hole power socket with a grounding wire (0 50m from the ground) shall be reserved, and its power supply reliability shall be compatible with the importance of the weak current system of power supply; Electrical shaft sockets: technical regulations for the design of indoor and outdoor power distribution in residential projects (for trial implementation)" CJS01-2013, 45.8. Electrical lighting and at least one single-phase three-hole power socket should be set up in the electrical shaft, and the power socket should be 0 5m 10m。Electrical shaft sockets: code for electrical design of residential buildings, JGJ 242—2011, 74.8. Electrical lighting and at least one single-phase three-hole power socket should be set up in the electrical shaft, and the power socket should be 0 from the ground5m~1.0m。Gymnasium sockets: Code for electrical design of sports buildings JGJ 354-2014, 71.6. The power distribution system of the sports process load shall comply with the following provisions: the distribution box and safety socket shall be set on the wall around the stadium competition venue, and the installation height of the socket shall not be less than 0 from the ground3m。The power distribution box of the timing and scoring device for swimming, diving, water polo and synchronized swimming should be located in the control room of the timing and scoring device; When there are power boxes, power socket boxes, and special signal boxes around the pool, the waterproof and moisture-proof type should be used, and the bottom margin should not be less than 03m;Socket in the comprehensive pipe gallery: technical code for the engineering of the urban comprehensive pipe gallery GB 50838-2015, 73.5. AC 220V 380V maintenance sockets with residual current action protection devices should be set up in the comprehensive pipe gallery, and the spacing along the sockets should not be greater than 60m. The capacity of the maintenance socket should not be less than 15kw, and the installation height should not be less than 05m。Power sockets for electric cooker consoles for the elderly: Architectural design standards for care facilities for the elderly" JGJ 450-2018, 73.7. The power socket should be a safety power socket. The height of the power socket in the living room should be 060m~0.80m;The height of the power socket of the electric cooking console for the elderly should be 0 from the ground90m~1.10m。

Sockets in humid places: Code for design of power distribution of general electrical equipment GB 50055-2011, 80.6. In wet places, sockets with splash-proof electrical accessories should be used, and the installation height should not be less than 1 from the ground5m。Elevator pit socket: code for electrical design of residential buildings" JGJ 242-2011, 82.7. The elevator pit should be provided with a single-phase three-hole power socket with a protection level of not less than IP54, and the power supply of the power socket can be connected nearby, and the bottom margin of the power socket should be 15m。Elevator pit socket: standard for electrical design of civil buildings GB 51348-2019, 93.Article 6 states that the lighting switch of the elevator pit can be set at the height of the IM. The installation height of the pit socket can be about 1m, which is mainly used for maintenance. Roof walking trolley socket: electrical design standard for civil buildings GB 51348-2019, 98.3. The electrical design of the window cleaning machine shall comply with the following provisions: the outdoor power supply socket of the roof walking trolley shall be set up every 10m 15m, and its protection level shall meet IP65 and above, and the installation height shall be set at a distance of 0 from the roof5m and above; Garbage station socket: "City Appearance and Sanitation Project Specification" GB 55013-2021, 40.Article 14 states that the power switch and socket in the operation area of the garbage transfer station should be set up from the ground 1More than 5m, the protection level of power switch and socket should not be lower than IP55; Residential TV Sockets: Code for Electrical Design of Residential Buildings JGJ 242-2011, 112.3. Two-way transmission TV sockets should be used in residential suites. The TV socket should be concealed, and the height of the bottom margin of the TV socket should be 03m~1.0m。Residential ** socket: code for electrical design of residential buildings" JGJ 242-2011, 113.3. RJ45** sockets should be used in the residential suite. **The socket should be concealed, and the height of the bottom margin of the socket should be 03m~0.5m, the height of the bottom margin of the ** socket in the bathroom should be 10m~1.3m。Residential Optical Fiber Information Socket: Code for Electrical Design of Residential Buildings JGJ 242-2011, 114.3. RJ45 information socket or optical fiber information socket should be used in each residence. The information socket should be concealed, and the height of the bottom margin of the information socket should be 03m~0.5m。Multi-user information socket box: Code for engineering design of integrated wiring system" GB 50311-2016, 71.3CP assembly point box, multi-user information socket box should be installed on the introduction side of the conduit and easy to maintain the column and load-bearing wall, etc., the bottom edge of the box should be 500mm from the ground, when installed in the wall, the upper part of the column or the ceiling, the height from the ground should not be less than 1800mm. Work area information socket: "Electrical Design Standard for Civil Buildings" GB 51348-2019, 216.1. The installation of the information socket in the work area should comply with the following provisions: the height of the bottom margin of the information socket on the wall or column from the ground should be 03m;In the place where the workbench is set up, the information socket should be installed above the workbench. Workspace Information Socket: Code for Engineering Design of Integrated Wiring System GB 50311-2016, 71.1. The installation of the information socket in the work area shall comply with the following provisions: the height of the bottom of the information socket box from the ground should be 300mm. The bottom distance of the information socket box installed on the side partition surface of the workbench and the adjacent wall should be 10m。Multi-user information socket box: standard for electrical design of civil buildings GB 51348-2019, 216.3. The assembly point (CP) box, multi-user information socket box, and user unit information distribution box should be set up in the fixed position of the building, and the height of the bottom margin from the ground should not be less than 0 when installed on the wall or column5m。Floor Information Wire Box: Electrical Design Standard for Civil Buildings GB 51348-2019, 266.10. The floor information box should be concealed, and the bottom margin of the box should be 300mm, and the installation height should be the same as that of the nearby concealed power socket. Gymnasium sockets: Code for electrical design of sports buildings JGJ 354-2014, 71.6. The power distribution system of the sports process load shall comply with the following provisions: the distribution box and safety socket shall be set on the wall around the stadium competition venue, and the installation height of the socket shall not be less than 0 3m from the ground. The power distribution box of the timing and scoring device for swimming, diving, water polo and synchronized swimming should be located in the control room of the timing and scoring device; When there are power boxes, power socket boxes, and special signal boxes around the pool, the waterproof and moisture-proof type should be used, and the bottom margin should not be less than 03m;Socket in the comprehensive pipe gallery: technical code for the engineering of the urban comprehensive pipe gallery GB 50838-2015, 73.5. AC 220V 380V maintenance sockets with residual current action protection devices should be set up in the comprehensive pipe gallery, and the spacing along the sockets should not be greater than 60m. The capacity of the maintenance socket should not be less than 15kw, and the installation height should not be less than 05m。

Related Pages