Overview of MURR Power Emparro AccuControl UPS parameters
MURR Electronics is a researcher in the development, manufacture and sale of automation solutions. Our products can be divided into four core product lines: Power & Control, Interfaces, Cable Connectors and IO Systems.
Murrelektronik is always customer-oriented, ensuring that our customized solutions are best suited to your application.
Emparro AccuControl UPS Power Supply:
The Emparro AccuControl UPS module completes the high-performance EMPARRO power supply system. In the event of a power failure, it automatically switches to battery power to prevent machine downtime. The investment in a UPS system usually pays for itself the first time downtime is avoided.
An external lead-acid battery with a capacity of up to 40 Ah ensures a long bridging time. UPS modules are available in 20 A or 40 A systems. The Emparro AccuControl can be assembled without the use of tools and is maintenance-free. Because it is only 65 mm wide, the 20A model requires very little space in the control cabinet.
Technical parameters: battery type sealed lead-acid battery.
The minimum load capacity of the signal contacts is 5 V, 1 mA
Maximum signal contact load capacity of 30 V, 100 mA
The maximum charge is 40 ah
Electrical Data |Input.
Shutdown input voltage DC 24 V
The power off input minimum input voltage DC 6 V
The maximum input voltage DC shutdown input is 45 V
The minimum input voltage DC 21,6 V
The maximum input voltage DC is 30 V
The maximum input current DC 23 A
Maximum charging current 2,5 A
Potential-free switch input Yes.
Sensor type KTY 81-210 (art..)no. 89600)
Electrical Data |Output.
The minimum output voltage DC 19,2 V
Maximum output voltage DC 27,7 V
Adjustable output voltage Yes.
output current max. 20 a
Advantage: Prevent machine downtime by switching to battery operation without interruption in the event of a power failure.
Maximum service life is achieved by temperature-controlled battery charging.
High operational reliability thanks to comprehensive control and diagnostic options as well as state-of-the-art maintenance.
The IPC's shutdown function prevents data loss with easy-to-use computer software.
MURR Part of the model:
Overview of MURR Power Emparro AccuControl UPS parameters