Several parking processes involved in the ACS880 lifting software and the time delay after parking are as follows:
21.07 Zero Speed Delay, set from 0 to 30,000ms. The motor stops reaching parameter 2106 After setting the zero speed, start timing, within the timing time, the inverter has an output, and the motor is electrified. When the timing ends, the inverter stops output. This feature can be used when the drive needs to start up quickly and frequently.
21.12 Continuous Magnetization Command: Continuous Magnetization Current Enables, Off, and Excitation Current is Not Maintained.
on, the excitation current is continuously active.
44.212.00, which is determined by 44 sets of parameters.
44.13 brake close delay, set from 0 to 60s. After the brake closing command is issued, the time when the inverter stops modulating the output.
44.15 brake close level delay, during the parking process, the motor speed is reduced to 44After setting the speed of 14, start the timing, generally 0After 2s, after the timer is over, XRO1 will issue a command to close the brake.
44.16 brake reopen delay, set the range of 0 to 10s, after the last stop brake closing command is issued, start timing, within the timing time, if the start command is received, the motor excites, but does not open the brake, until the timing ends, open the brake, start running.
44.211 extended runtime, 0 to 3600s. Delay excitation, motor stops, after the brake closing command is issued, start timing, within the timing time, the motor is live, and the excitation is maintained. Timing time, parameter 44212.00 is 1 for bit 0. At the end of the timer, the bit is 0.
For the above delay, you can choose 1 or 2 according to your actual needs.